Electronic thermostat

DCT 010

Electronic thermostat with integrated switch module for controlling DC devices in casings and enclosures. Switches all common loads in enclosure applications: Heating, fans, signal transmitters, etc. Normally open versions (NO) in two versions with a wide temperature setting range. Normally closed versions (NC) with secondary switch function: 65 % RH fixed setting.

  • Internal switch module with high DC switching capacity
  • Adjustable temperature
  • Small hysteresis
  • External sensor
CEUKCAEACULVDE

Overview technical data

Device typeThermostats DC applications
Contact typeMOSFET
Protection typeIP20
Operating displayLED
External sensorCable 2 m with snap-in male connector
CasingPlastic to UL94 V-0, light grey
AC/DCDC
Operating voltage20 V - 56 V
Operating voltage tolerance18 V - 61 V
Inrush current maximum24 A
Inrush current duration 10 s
Power consumption 1 W
Reference voltage ohmic maximum20...56 VDC
Reaction time 5 s
Service life>100000 cycles
Switching differential 3 K
Switching differential tolerance ± 1 K
Operating humidity ≤90 % RH
Storage humidity ≤90 % RH
Storage temperature-40 °F - 176 °F
Connection6-pole clamp: stranded wire 1.5 mm² (AWG 16) max. 2.5 mm² (AWG 12)
MountingClip for 35 mm DIN rail, EN 60715
Height 3.7 in
Width 2.1 in
Depth 1.7 in
Weight 4.2 oz
NoteSecondary switch function: Versions with a secondary switch function can also react to humidity and thus offer greater contactor protection for the electronics. Switching differential: 4% rH (+1% tolerance) at +25°C (+77°F), 50% rH. Wire end ferrules must be used for connections with stranded wires.

Product variants

Article numberSetting rangeSwitching capacitySwitching current ohmicSetting range 2 minimumOperating temperatureDesignRequestCADDatasheet
01011.0-4114 °F - 122 °F13 A (DC) 13 A65 % RH-40 °F - 122 °FNormally closed (NC)
DCT010-01011.0-41-Datasheet-EN-US.pdf
01011.0-2114 °F - 122 °F13 A (DC) 13 A-40 °F - 122 °FNormally open (NO)
DCT010-01011.0-21-Datasheet-EN-US.pdf
01011.0-2232 °F - 140 °F11 A (DC) 11 A-40 °F - 140 °FNormally open (NO)
DCT010-01011.0-22-Datasheet-EN-US.pdf
01011.0-4232 °F - 140 °F11 A (DC) 11 A65 % RH-40 °F - 140 °FNormally open (NO)
DCT010-01011.0-42-Datasheet-EN-US.pdf

Certificates

Your direct contact