STEGO enclosure heaters and filter fans heat and cool your control cabinet. Thermostats, hygrostats and sensors complete temperature and humidity control systems in your technical application. STEGO offers matching lighting and accessories.
Suche
dct010-elektronischer-thermostat-oeffner-schlieįer-electronic-thermostat-feature
dct010-thermostat-oeffner-feature
dct010-thermostat-schlieįer-feature
2018_dcf010_dct010_drawing
ETF012-1-DCT010-DCF010-drawing-external-sensor
DCT010-diagram
DCT010-connection-example

Electronic thermostat

DCT 010

Electronic thermostat with integrated switch module for controlling DC devices in enclosures and casings. Switches all common loads in enclosure applications: Heating, fans, signal transmitters, etc. Normally open versions (NO) in two versions with a wide temperature setting range. Normally closed versions (NC) with secondary switch function: 65 % RH fixed setting.

  • Internal switch module with high DC switching performance
  • Adjustable temperature
  • Small hysteresis
  • External sensor
CEUKCAEACULVDE

Overview technical data

Device typeThermostats; DC applications
Contact typeMOSFET
Protection typeIP20
Operating displayLED
External sensorCable 2 m with snap-in male connector
CasingPlastic to UL94 V-0, light grey
AC/DCDC
Operating voltage20 V - 56 V
Inrush current24 A
Inrush current duration10 s
Power consumption1 W
Reference voltage ohmic20...56 VDC
Reaction time5 s
Service life>100000 cycles
Switching differential3 K
Switching differential tolerance± 1 K
Operating humidity≤90 % RH
Storage humidity≤90 % RH
Storage temperature-40 °C - 80 °C
Connection6-pole clamp: stranded wire 1.5 mm² (AWG 16); max. 2.5 mm² (AWG 12)
MountingClip for 35 mm DIN rail, EN 60715
Height93 mm
Width53 mm
Depth44 mm
Weight120 g
NoteSecondary switch function: Versions with a secondary switch function can also react to humidity and thus offer greater contactor protection for the electronics. Switching differential: 4% rH (+1% tolerance) at +25 °C (+77 °F), 50% rH. Wire end ferrules must be used for connections with stranded wires.

Product variants

Article numberSetting rangeSwitching capacitySwitching current ohmicSetting range 2Operating temperatureDesignInteractions
01011.0-41-10 °C - 50 °C13 A (DC)13 A65 % RH-40 °C - 50 °CContact breaker (NC)
01011.0-21-10 °C - 50 °C13 A (DC)13 A-40 °C - 50 °CNormally open (NO)
01011.0-220 °C - 60 °C11 A (DC)11 A-40 °C - 60 °CNormally open (NO)
01011.0-420 °C - 60 °C11 A (DC)11 A65 % RH-40 °C - 60 °CNormally open (NO)

Certificates