Thermostat switch (NC)

KTO 111

The mechanical NC thermostat opens when the temperature rises and is used to control heaters or to switch signal transmitters when the temperature undershoots. The use of push-in terminals prevents the supply lines from coming loose.

  • Fixed supply lines thanks to push-in terminals
  • Time saving thanks to tool-free connection
  • Large adjustment wheel enables convenient adjustablility
  • Optimized air inlets
  • Can be used at altitudes of up to 5000 meters
CEUKCAEACULVDE

Overview technical data

Device typeThermostats
Contact typeSnap-action contact
SensorThermostatic bimetal
Protection typeIP20
CasingPlastic to UL94 V-0, light grey
AC/DCAC DC
Maximum operating voltage toleranceAC 250 V (VDE), AC 120 V (UL) V
Maximum inrush current16 A
Inrush current duration 10 s
Reference voltage ohmic maximum250 VAC
Reference voltage 2 ohmic maximum120 VAC
Switching current inductive 2 A
Reference voltage inductive maximum250 VAC
Maximum reference voltage 2120 VAC
Switching current DC ohmic 1 A
Reference voltage DC ohmic maximum30 VDC
Minimal switching capacity 0.48 W
Minimum reference voltage24 V
Switching current 20 mA
Service life>100000 cycles
Switching differential 7 K
Switching differential tolerance ± 4 K
Operating temperature-49 °F - 176 °F
Operating humidity ≤90 % RH
Storage humidity ≤90 % RH
Storage temperature-49 °F - 176 °F
Connection2 push-in terminals Rigid wire cable 2.5 mm² (AWG 14) Stranded wire 1.5 mm² (AWG 16)
DesignNormally closed (NC)
MountingClip for 35 mm DIN rail, EN 60715
Height 2.4 in
Width 1.3 in
Depth 1.6 in
Weight 1.4 oz
NoteOvervoltage category: II: up to 5000 m III: up to 2000 m. The controller's contact system is exposed to the effects of the environment, which can change the contact resistance. This can lead to a voltage drop and/or self-heating of the contacts. Stripped length of rigid wire cable: 8 to 12 mm. Wire end ferrules (square or trapezoidal crimped) must be used for connections with stranded wires. Length of wire end ferrule: 8 mm or 12 mm. The height of the current has an influence on the tolerance accuracy, values specified: Switching resistive load (switching inductive load).
CCCCQC

Product variants

Article numberSetting rangeSwitching capacitySwitching current ohmicRequestCADDatasheet
11100.0-0032 °F - 140 °FAC 250 V: 10 (2) A AC 120 V: 15 (2) A DC 24-72V: 30 W 10 A
KTO111-11100.0-00-Datasheet-EN-US.pdf
11100.0-0268 °F - 176 °FAC 250 V: 3 (2) A AC 120 V: 3 (2) A DC 24-72V: 30 W 3 A
KTO111-11100.0-02-Datasheet-EN-US.pdf
11100.0-0114 °F - 122 °FAC 250 V: 10 (2) A AC 120 V: 15 (2) A DC 24-72V: 30 W 10 A
KTO111-11100.0-01-Datasheet-EN-US.pdf
11100.9-0032 °F - 140 °FAC 250 V: 10 (2) A AC 120 V: 15 (2) A DC 24-72V: 30 W 10 A
KTO111-11100.9-00-Datasheet-EN-US.pdf
11100.9-0114 °F - 122 °FAC 250 V: 10 (2) A AC 120 V: 15 (2) A DC 24-72V: 30 W 10 A