Suche
zr011-zwillings-thermostat-dual-thermostat-feature
2017_04_zr011_connectionexample
zr011-dual-thermostat-technical-drawing
zr011-dual-thermostat-wiring-diagram-diagramm

Dual thermostat

ZR 011

Thermostat contact breaker (NC, normally closed) and thermostat normally open contact (NO, normally closed) in one casing. Unlike thermostats with change-over contact, the double thermostat switches independently. This allows heating and cooling devices to be switched in different temperature ranges.

  • Contact breaker (NC, heating) and normally open contact (NO, cooling) in one casing
  • Jump contact enables independent switching
  • Temperatures separately adjustable
  • High switching capacity
  • Clip fixing
CEUKCAEACULVDECSACQC

Overview technical data

Device typeThermostats
Contact typeSnap-action contact
SensorThermostatic bimetal
Protection typeIP20
CasingPlastic to UL94 V-0, light grey
AC/DCAC DC
Operating voltage tolerance maximumAC 250 V (VDE), AC 120 V (UL) V
Inrush current maximum16 A
Inrush current duration 10 s
Switching capacityAC 250 V: 10 (2) A AC 120 V: 15 (2) A DC 24-72V: 30 W
Switching current ohmic 10 A
Switching current 2 ohmic 15 A
Reference voltage ohmic maximum250 VAC
Reference voltage 2 ohmic maximum120 VAC
Switching current inductive 2 A
Reference voltage inductive maximum250 VAC
Reference voltage 2 maximum120 VAC
Switching current dc ohmic 1 A
Reference voltage dc ohmic maximum30 VDC
Minimal switching capacity 0,48 W
Reference voltage minimum24 V
Switching current 20 mA
Service life>100000 cycles
Switching differential 7 K
Switching differential tolerance ± 4 K
Operating temperature-45 °C - 80 °C
Operating humidity ≤90 % RH
Storage humidity ≤90 % RH
Storage temperature-45 °C - 80 °C
Torque 0,5 Nmmax.
Connection4-pole clamp, torque 0.5 Nm max: Rigid wire cable 2.5 mm² (AWG 14) Stranded wire1 1.5 mm² (AWG 16)
MountingClip for 35 mm DIN rail, EN 60715
Height 67 mm
Width 50 mm
Depth 46 mm
Weight 90 g
NoteCSA approved 01176.0-00 and 01176.0-01 for controlling heat exchangers and fans (e.g. LE 019) and as an alarm or signaling contact for monitoring the internal temperature of the control cabinet. Wire end ferrules must be used for connections with stranded wires. The controller's contact system is exposed to environmental influences, which can change the contact resistance. This can lead to a voltage drop and/or self-heating of the contacts.
CCCCQC

Product variants

Article numberSetting rangesetting_range_2DesignRequestCADDatasheet
01172.0-000 °C - 60 °C0 °C - 60 °CContact breaker (NC) normally open contact (NO)
ZR011-01172.0-00-Datasheet-EN-SE.pdf
01172.0-0132 °F - 140 °F32 °F - 140 °FContact breaker (NC) normally open contact (NO)
ZR011-01172.0-01-Datasheet-EN-SE.pdf
01175.0-00-10 °C - 50 °C20 °C - 80 °CContact breaker (NC) normally open contact (NO)
ZR011-01175.0-00-Datasheet-EN-SE.pdf
01176.0-000 °C - 60 °C0 °C - 60 °CNormally open (NO) Normally closed (NO)
ZR011-01176.0-00-Datasheet-EN-SE.pdf

Certificates