Dual thermostat

ZR 011

Normally closed (NC) and normally open (NO) thermostats in one casing. Unlike thermostats with changeover contacts, the double thermostat switches independently. This allows heating and cooling devices to be switched in different temperature ranges.

  • Normally closed (NC, heating) and normally open (NO, cooling) in one casing
  • Snap-action contact enables independent switching
  • Temperatures can be adjusted separately
  • High switching capacity
  • Clip mounting
CEUKCAEACULVDECSACQC

Overview technical data

Device typeThermostats
Contact typeSnap-action contact
SensorThermostatic bimetal
Protection typeIP20
CasingPlastic to UL94 V-0, light grey
AC/DCAC;DC
Operating voltage toleranceAC 250 V (VDE), AC 120 V (UL) V
Inrush current16 A
Inrush current duration10 s
Switching capacityAC 250 V: 10 (2) A; AC 120 V: 15 (2) A; DC 24-72V: 30 W
Switching current ohmic10 A
Switching current 2 ohmic15 A
Reference voltage ohmic250 VAC
Reference voltage 2 ohmic120 VAC
Switching current inductive2 A
reference_voltage_inductive250 VAC
Reference voltage 2120 VAC
Switching current dc ohmic1 A
Reference voltage dc ohmic30 VDC
Minimal switching capacity0,48 W
Reference voltage24 V
Switching current20 mA
Service life>100000 cycles
Switching differential7 K
Switching differential tolerance± 4 K
Operating temperature-45 °C - 80 °C
Operating humidity≤90 % RH
Storage humidity≤90 % RH
Storage temperature-45 °C - 80 °C
Torque0,5 Nmmax.
Connection4-pole clamp, torque 0.5 Nm max: Rigid wire cable 2.5 mm² (AWG 14) Stranded wire1 1.5 mm² (AWG 16)
MountingClip for 35 mm DIN rail, EN 60715
Height67 mm
Width50 mm
Depth46 mm
Weight90 g
NoteCSA approved;01176.0-00 and 01176.0-01 for controlling heat exchangers and fans (e.g. LE 019) and as an alarm or signalling contact for monitoring the internal enclosure temperature. Wire end ferrules must be used for connections with stranded wires. The controller's contact system is exposed to environmental influences, which can change the contact resistance. This can lead to a voltage drop and/or self-heating of the contacts.
CCCCQC

Product variants

Article numberSetting rangesetting_range_2DesignInteractions
01172.0-000 °C - 60 °C0 °C - 60 °CNormally closed (NC); Normally open (NO)
01172.0-0132 °F - 140 °F32 °F - 140 °FNormally closed (NC); Normally open (NO)
01175.0-00-10 °C - 50 °C20 °C - 80 °CNormally closed (NC); Normally open (NO)
01176.0-000 °C - 60 °C0 °C - 60 °CNormally open (NO); Normally closed (NO)