STEGO enclosure heaters and filter fans heat and cool your control cabinet. Thermostats, hygrostats and sensors complete temperature and humidity control systems in your technical application. STEGO offers matching lighting and accessories.
Suche
ftd011-zwillings-fix-thermostat-tamper-proof-dual-thermostat-feature
2013_ftd011_drawing
FTD011-diagram
FTD011-connection-example

Tamper-proof dual thermostat

FTD 011

Fixed thermostat contact breaker (NC) and thermostat normally open contact (NO) in one casing. Unlike thermostats with change-over contact, the double thermostat switches independently. This allows heating and cooling devices to be switched in different temperature ranges.

  • Contact breaker (NC, normally closed, heating) and normally open contact (NO, normally closed, cooling) in one casing
  • Jump contact enables independent switching
  • Fixed temperature setting
  • High switching accuracy
  • Clip fixing
CEUKCAEACULVDE

Overview technical data

Device typeThermostats
Setting rangefirm
Contact typeSnap-action contact
SensorThermostatic bimetal
Protection typeIP20
CasingPlastic to UL94 V-0, light grey
AC/DCAC;DC
Inrush current16 A
Inrush current duration10 s
Switching capacityAC 250 V: 5 (1.6) A; AC 120 V: 10 (2) A; DC 24-72 V: 30 W
Switching current ohmic5 A
Switching current 2 ohmic10 A
Reference voltage ohmic250 VAC
Reference voltage 2 ohmic120 VAC
Switching current inductive1,6 A
Switching current 2 inductive2 A
Reference voltage inductive maximum250 VAC
Reference voltage 2120 VAC
Switching current dc ohmic1 A
Reference voltage dc ohmic30 VDC
Minimal switching capacity0,48 W
Reference voltage24 V
Switching current20 mA
Service life>100000 cycles
Switch-off temperature15 °C
Switch-off temperature tolerance± 5 K
Switch-off temperature 2 tolerance± 6 K
Switch-on temperature5 °C
Switch-on temperature tolerance± 5 K
Switch-on temperature 2 tolerance± 7 K
Operating temperature-40 °C - 80 °C
Operating humidity≤90 % RH
Storage humidity≤90 % RH
Storage temperature-45 °C - 80 °C
Torque0,8 Nm max.
Connection2-pole clamp: Rigid wire/stranded wire 2.5 mm² (AWG 14)
DesignContact breaker (NC); normally open contact (NO)
MountingClip for 35 mm DIN rail, EN 60715
Height47 mm
Width63 mm
Depth33 mm
Weight40 g
NoteOther switch-on/switch-off temperatures on request. Wire end ferrules must be used for connections with stranded wires. Switching of resistive load (switching of inductive load).

Product variants

Article numberSwitch-off temperature 2Switch-on temperature 2Interactions
01163.0-02+25 °C35 °C
01163.0-00+40 °C50 °C

Certificates