Tamper-proof dual thermostat

FTD 011

Fixed thermostat contact breaker (NC) and thermostat normally open contact (NO) in one casing. Unlike thermostats with change-over contact, the double thermostat switches independently. This allows heating and cooling devices to be switched in different temperature ranges.

  • Contact breaker (NC, normally closed, heating) and normally open contact (NO, normally closed, cooling) in one casing
  • Jump contact enables independent switching
  • Fixed temperature setting
  • High switching accuracy
  • Clip fixing
CEUKCAEACULVDE

Overview technical data

Device typeThermostats
Setting rangefirm
Contact typeSnap-action contact
SensorThermostatic bimetal
Protection typeIP20
CasingPlastic to UL94 V-0, light grey
AC/DCAC DC
Operating voltage tolerance maximumAC 250 V (VDE), AC 120 V (UL) V
Inrush current maximum16 A
Inrush current duration 10 s
Switching capacityAC 250 V: 5 (1.6) A AC 120 V: 10 (2) A DC 24-72V: 30 W
Switching current ohmic 5 A
Switching current 2 ohmic 10 A
Reference voltage ohmic maximum250 VAC
Reference voltage 2 ohmic maximum120 VAC
Switching current inductive 1,6 A
Switching current 2 inductive 2 A
Reference voltage inductive maximum250 VAC
Reference voltage 2 maximum120 VAC
Switching current dc ohmic 1 A
Reference voltage dc ohmic maximum30 VDC
Minimal switching capacity 0,48 W
Reference voltage minimum24 V
Switching current 20 mA
Service life>100000 cycles
Switch-off temperature 15 °C
Switch-off temperature tolerance ± 5 K
Switch-off temperature 2 tolerance ± 6 K
Switch-on temperature 5 °C
Switch-on temperature tolerance ± 5 K
Switch-on temperature 2 tolerance ± 7 K
Operating temperature-40 °C - 80 °C
Operating humidity ≤90 % RH
Storage humidity ≤90 % RH
Storage temperature-45 °C - 80 °C
Torque 0,8 Nmmax.
Connection2-pole clamp, torque 0.8 Nm max: Rigid wire/stranded wire 2.5 mm² (AWG 14)
DesignContact breaker (NC) normally open contact (NO)
MountingClip for 35 mm DIN rail, EN 60715
Height 47 mm
Width 63 mm
Depth 33 mm
Weight 40 g
NoteOther switch-on/switch-off temperatures on request. Wire end ferrules must be used for connections with stranded wires. Switching of resistive load (switching of inductive load).

Product variants

Article numberSwitch-off temperature 2Switch-on temperature 2RequestCADDatasheet
01163.0-02 25 °C 35 °C
FTD011-01163.0-02-Datasheet-EN-SE.pdf
01163.0-00 40 °C 50 °C
FTD011-01163.0-00-Datasheet-EN-SE.pdf