Tamper-proof dual thermostat

FTD 011

Fixed thermostat contact breaker (NC) and thermostat normally open contact (NO) in one casing. Unlike thermostats with change-over contact, the double thermostat switches independently. This allows heating and cooling devices to be switched in different temperature ranges.

  • Contact breaker (NC, normally closed, heating) and normally open contact (NO, normally closed, cooling) in one casing
  • Jump contact enables independent switching
  • Fixed temperature setting
  • High switching accuracy
  • Clip fixing
CEUKCAEACULVDE

Overview technical data

Device typeThermostats
Setting rangefirm
Contact typeSnap-action contact
SensorThermostatic bimetal
Protection typeIP20
CasingPlastic to UL94 V-0, light grey
AC/DCAC;DC
Operating voltage toleranceAC 250 V (VDE), AC 120 V (UL) V
Inrush current16 A
Inrush current duration10 s
Switching capacityAC 250 V: 5 (1.6) A; AC 120 V: 10 (2) A; DC 24-72V: 30 W
Switching current ohmic5 A
Switching current 2 ohmic10 A
Reference voltage ohmic250 VAC
Reference voltage 2 ohmic120 VAC
Switching current inductive1,6 A
Switching current 2 inductive2 A
reference_voltage_inductive250 VAC
Reference voltage 2120 VAC
Switching current dc ohmic1 A
Reference voltage dc ohmic30 VDC
Minimal switching capacity0,48 W
Reference voltage24 V
Switching current20 mA
Service life>100000 cycles
Switch-off temperature15 °C
Switch-off temperature tolerance± 5 K
Switch-off temperature 2 tolerance± 6 K
Switch-on temperature5 °C
Switch-on temperature tolerance± 5 K
Switch-on temperature 2 tolerance± 7 K
Operating temperature-40 °C - 80 °C
Operating humidity≤90 % RH
Storage humidity≤90 % RH
Storage temperature-45 °C - 80 °C
Torque0,8 Nmmax.
Connection2-pole clamp, torque 0.8 Nm max: Rigid wire/stranded wire 2.5 mm² (AWG 14)
DesignContact breaker (NC); normally open contact (NO)
MountingClip for 35 mm DIN rail, EN 60715
Height47 mm
Width63 mm
Depth33 mm
Weight40 g
NoteOther switch-on/switch-off temperatures on request. Wire end ferrules must be used for connections with stranded wires. Switching of resistive load (switching of inductive load).

Product variants

Article numberSwitch-off temperature 2Switch-on temperature 2Interactions
01163.0-02+25 °C35 °C
01163.0-00+40 °C50 °C

Certificates