STEGO enclosure heaters and filter fans heat and cool your control cabinet. Thermostats, hygrostats and sensors complete temperature and humidity control systems in your technical application. STEGO offers matching lighting and accessories.
Suche
MFR-012-2-feature
MFR-012-2
MFR-012-2-front-and-back
MFR-012-2-technical-drawing

New: Mechanical hygrostat

MFR 012

The hygrostat is used to prevent condensate and regulates heating and fans. From a critical relative humidity of 65 %, the temperature is increased so that the relative air humidity decreases and condensate is prevented from forming.

  • Adjustable relative air humidity
  • Changeover contact (heating or cooling)
  • High switching capacity
  • Clip mounting
CEUKCAEACUL

Overview technical data

Device typeHygrostat
Setting range30 % RH - 95 % RH
Contact typeSnap-action contact
Protection typeIP30
CasingPlastic to UL94 V-0, light grey
AC/DCAC;DC
Inrush current16 A
Inrush current duration10 s
Switching capacityAC 5 A;DC 20 W
Switching current ohmic10 A
Reference voltage ohmic250 VAC
Reference voltage 2 ohmic120 VAC
Switching current dc ohmic0,6 A
Reference voltage dc ohmic30 VDC
Reference voltage20 V
Switching current0,1 A
Service life10 A; 10000 cycles 6 A; 50000 cycles
Switching differential4 % RH
Switching differential tolerance± 1,5 % RH
Operating temperature0 °C - 60 °C
Operating humidity≤95 % RH
Storage humidity≤95 % RH
Storage temperature-40 °C - 60 °C
Connection typeConnection terminal (push-in)
Connection3 x stranded wire 1.0 - 2.5 mm² (with wire end ferrule) and rigid wire 1.0 - 2.5 mm²
DesignChanger
MountingClip for 35 mm DIN rail, EN 60715
Height84 mm
Width35 mm
Depth43 mm
Weight45 g
NoteSwitching differential referred to 50 % rH. Wire end ferrules must be used for connections with stranded wires.